Inspection and maintenance service for fire extinguisher system
Lam Son JSC is a local partner of Eversafe and Lingjack, offering equipment and parts replacement, fire extinguishers and routine maintenance on demand.
MAINTENANCE PROCEDURE FOR FIRE EQUIPMENT :
- Check annual portable fire extinguishers and trolleys.
- Check CO2 fire extinguishing systems, FM 200 system, Dry powder, Foam, Water mist, Wet chemical fire extinguishing system for kitchen.
- Check hose system, water cannons, spray nozzle.
- Analyze foam concentrates samples.
1. Portable fire extinguisher
- Preliminary test for fire extinguishers.
- Check the outside condition including the body, handle, nozzle, valve. Replace or repair if damaged.
- Check Agent and propellant, replace it if necessary.
- Check Hydrostatic Test Date, test again if it expires.
- Paste checking stamps, hanging periodic inspection cards.
- Make report and issue Certificate after completion.
2. Fixed CO2 fire-extinguishing systems
* Annual inspection
- Check and weigh the CO2 container.
- Check the activation gas tank if available.
- Check audible/visual alarm system, fan stop.
- Blowing by compressed air from CO2 room to all nozzles.
* 5 yearly inspection
- Check, test Time Delay Unit.
- Manifold leakage tested by applying dry working air.
- Pilot line pressure tested at maximum working pressure.
- Check inside the main valve.
* 10 yearly inspection
- Pressure test CO2 cylinder.
- Replace flexible hose (If applicable).